Test
Sequence
|
Parameter
for
Evaluation |
Test
Voltage Highest Voltage
Umax (Kv) |
Result |
| |
|
7.2 |
12 |
24 |
36 |
|
|
Conductor
Resistance |
1
S : 10810
(Parts) |
- |
- |
- |
- |
Resistance
shall be computed and corrected at
200C
and recorded |
| Impact
Test |
Clause
6.1 of
IS : 13573 |
- |
- |
- |
- |
There
shall be no visible damage |
| A.C.
Voltage withstand (Dry) |
1
Min |
27 |
35 |
55 |
75 |
No
breakdown and no flashover |
| A.C.
Voltage withstand (Wet) |
1
Min |
20 |
28 |
50 |
70 |
No
breakdown and no flashover |
| Partial
Discharge |
--- |
2
Uo |
2
Uo |
2
Uo |
2
Uo |
≤ 20pC |
Impulse
Voltage
withstand |
10
positive and 10 negative, 1.2 / 50 uS,
between each conductor and the grounded
screen |
60 |
75 |
125 |
170 |
No
breakdown and no flashover |
| Load
Cycling |
3
cycles 5h heating, 3h cooling Conductor
temperature: 5+ operating temperature |
9.5 |
16 |
32 |
50 |
No
breakdown and no flashover |
| Partial
Discharge |
--- |
2
Uo |
2
Uo |
2
Uo |
2
Uo |
≤ 20pC |
| Load
Cycling |
60
cycles 5h heating, 3h cooling Conductor
temperature: 5+ operating temperature |
9.5 |
16 |
32 |
50 |
No
breakdown and no flashover |
| Thermal
Short Circuit |
1
sec symmetrical fault with conductor
temperature as for cable specification
1 sec earth fault with screen or armour temperature as for cable
specification |
- |
- |
- |
- |
No
visible signs of damage |
| Load
cycling |
63
cycles 5h heating, 3h cooling Conductor
temperature: 5+ operating temperature |
9.5 |
16 |
32 |
50 |
No
breakdown and no flashover |
| Conductor
Resistance |
--- |
- |
- |
- |
- |
10%
more than initial reading |
| Impulse
voltage withstand |
10
positive and 10 negative, 1.2/ 50mS,
between each conductor and the grounded
screen |
60 |
75 |
125 |
170 |
No
breakdown and no flashover |
| D.C
Voltage withstand |
30
min |
28 |
48 |
96 |
144 |
No
breakdown and no flashover |
| Humidity
indoor terminations |
Conductivity
70±10 m S/m, 300 hour spray rate:
litrel/m 3/h |
4.5 |
7.5 |
15 |
22.5 |
No
breakdown and no flashover, no visible
tracking and so erosion |
| Dynamic
short circuit |
63kA |
- |
- |
- |
- |
No
visible signs of damage |
| Salt-fog
outdoor termination |
Conductivity
1600±200mS/m, 1000 hour |
4.5 |
7.5 |
15 |
22.5 |
No
flashover |